TM0110 Page 1 of 22 Issue 1.00
SIRIUS II
2, 4 & 8 ZONE
CONVENTIONAL
FIRE ALARM CONTROL PANEL
INSTALLATION,
OPERATION AND
MAINTENANCE MANUAL
TM0110
PROPRIETARY RIGHTS NOTICE
The information contained in this manual is the property of Kidde Products Limited and may not be
reproduced or transmitted in any form or by any means, electronic, mechanical, photocopying, recording or
otherwise, nor stored in any retrieval system of any nature without the express written authority of
Kidde Products Limited.
Kidde Fire Protection is a trading brand of Kidde Products Limited
© Copyright 2007 Kidde Products Limited
Page view 0
1 2 3 4 5 6 ... 21 22

Summary of Contents

Page 1 - SIRIUS II

TM0110 Page 1 of 22 Issue 1.00 SIRIUS II 2, 4 & 8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL INSTALLATION, OPERATION AND MAINTENANC

Page 2 - TABLE OF CONTENTS

TM0110 Page 10 of 22 Issue 1.00 CHAPTER 3 INSTALLATION AND COMMISSIONING 3.1 GENERAL Installation of the fire detection and alarm system must

Page 3 - DESCRIPTION

TM0110 Page 11 of 22 Issue 1.00 Static discharges can be reduced by following these guidelines: 1. Always use conductive or anti-static container

Page 4

TM0110 Page 12 of 22 Issue 1.00 last device in each of the zone wirings, end of line resistors across auxiliary alarm circuits and fire outputs. Con

Page 5

TM0110 Page 13 of 22 Issue 1.00 polarised. Non-polarised sounders will show a sounder fault. The most common sounders are bells and electronic soun

Page 6

TM0110 Page 14 of 22 Issue 1.00 Figure 4: External Connections

Page 7

TM0110 Page 15 of 22 Issue 1.00 3.4 COMMISSIONING CAUTION The control panel may be damaged by removing and/or inserting cards, modules, or interc

Page 8 - OPERATION

TM0110 Page 16 of 22 Issue 1.00 Turn the mains supply off. Using the short lead supplied, connect the positive terminal of one battery to the nega

Page 9

TM0110 Page 17 of 22 Issue 1.00 ZONE ONE MAN TEST The ZONE ONE MAN TEST function allows the engineer to test zone FIRE responses from one or more z

Page 10 - CHAPTER 3

TM0110 Page 18 of 22 Issue 1.00 PANEL ALARM MODES The PANEL ALARM MODES function allows the engineer to configure the panel alarm circuits. When t

Page 11

TM0110 Page 19 of 22 Issue 1.00 CHAPTER 4 MAINTENANCE 4.1 GENERAL Maintenance of equipment external to the control panel will be detailed in t

Page 12

TM0110 Page 2 of 22 Issue 1.00 TABLE OF CONTENTS Chapter Page 1.0 Description 1.1 General Description 3 1.2 Display Panel 4 1.3

Page 13

TM0110 Page 20 of 22 Issue 1.00 CHAPTER 5 SPECIFICATIONS AND DATA 5.1 WIRING SPECIFICATION All system wiring should be screened and installed

Page 14

TM0110 Page 21 of 22 Issue 1.00 Power Supply Mains supply voltage 230V AC +/- 10% 50/60 Hz Internal power supply 28V DC Nominal Output Voltage r

Page 15

TM0110 Page 22 of 22 Issue 1.00 Maximum total sounder load Up to 500 mA each circuit (limit to 1A total) Maximum cable length per circuit 450 met

Page 16

TM0110 Page 3 of 22 Issue 1.00 CHAPTER 1 DESCRIPTION 1.1 GENERAL DESCRIPTION Sirius II is a conventional fire alarm control panel designed to

Page 17

TM0110 Page 4 of 22 Issue 1.00 1.2 DISPLAY PANEL All indications and controls are available via the Sirius II display panel (Figure 2). This inco

Page 18

TM0110 Page 5 of 22 Issue 1.00 FIRE ALARM The red FIRE ALARM light comes on when any zone is in a fire alarm condition. This light flashes 1 secon

Page 19 - MAINTENANCE

TM0110 Page 6 of 22 Issue 1.00 The following controls are available in Access Level 2: SILENCE / RESOUND ALARMS If the panel has a zone fire state,

Page 20 - SPECIFICATIONS AND DATA

TM0110 Page 7 of 22 Issue 1.00 1.5 EN 54 OPTIONAL FUNCTIONS WITH REQUIREMENTS The panel has the following optional functions: • Output to fire a

Page 21

TM0110 Page 8 of 22 Issue 1.00 CHAPTER 2 OPERATION 2.1 GENERAL Under normal operating conditions, the green POWER ON light is on and the zone

Page 22

TM0110 Page 9 of 22 Issue 1.00 2.4 DISABLEMENTS The disablement function allows the operator to disable several panel functions. The ZONE