TM0110 Page 8 of 22 Issue 1.00
CHAPTER 2
OPERATION
2.1 GENERAL
Under normal operating conditions, the green POWER ON light is on and the zone window lights are
off.
When a fire condition is detected, the applicable red zone fire light flashes, the red ALARM light
flashes, the red FIRE OUTPUT light comes on, the alarm sounder circuits are activated (unless
programmed off) and the buzzer on the panel sounds continuously.
If a fire indication shows in one or more zones and after the appropriate fire drill has been completed,
to silence the alarms:
enter Level 2 (the yellow ACCESS light comes on).
operate the SILENCE RESOUND ALARMS switch (the audible buzzer sounds intermittently, the
zone light, the FIRE OUTPUT light and the ALARM light stay on. The audible alarm circuits go off
and the fire output circuit remains active.)
When all zone fire conditions have been rectified, operate the SYSTEM RESET switch, (the panel
reverts to Level 1). If the fire condition still exists, the panel reverts to the alarm condition. To reset
the panel it may be necessary to clear smoke or heat from the detectors and to replace the glass in
the manual fire call point.
If a fault occurs, the applicable yellow zone fault light flashes, the applicable yellow SYSTEM FAULT,
COMMON FAULT or SOUNDER FAULT light flashes and the buzzer on the panel sounds
intermittently (one second on, three seconds off).
When in Access Level 2, all other panel operator functions can be accessed when the MENU and
then UP or DOWN switches are operated, ie:
TIME / DATE
DAY / NIGHT MODE
DISABLEMENTS
VIEW
2.2 TIME / DATE
This function allows the operator to enter a new date and time. In panel quiescent condition the day
and time are displayed on line 1 of the display. When a panel zone alarm condition occurs, the time
is displayed with the zone in alarm message. Panel Night to Day delay mode of operation relies on
the time for switch-over. To exit the time/date function at any time press the EXIT switch, or do not
operate any switch for 30 seconds.
2.3 DAY / NIGHT MODE
This function allows the operator to turn the Day / Night panel mode of operation (see page 18) on or
off. When enabled, this delays the operation of the panel alarms and fire outputs when zone fire
alarm events occur in the day. If enabled the OUTPUT DELAYS light is on.