TM0110 Page 20 of 22 Issue 1.00
CHAPTER 5
SPECIFICATIONS AND DATA
5.1 WIRING SPECIFICATION
All system wiring should be screened and installed to meet local regulations.
CABLE TYPES AND LIMITATIONS
To shield the panel from outside interference and ensure compliance with electromagnetic
regulations, we recommend screened cables are used throughout the installation.
MAINS WIRING
The requirements for the mains supply to the fire alarm panel is fixed wiring, using three core cable
(no less than 0.75 sq mm and no more than 2.5 sq mm) or a suitable three conductor system, fed
from an isolating switch fuse spur, fused at 3A.
ZONE WIRING
Cable 1.0 mm CSA Max length 600 metres
Cable 1.5 mm CSA Max length 1 kilometre
ALARM WIRING
Cable 1.0 mm CSA Max length 300 metres
Cable 1.5 mm CSA Max length 450 metres
FIRE OUTPUT WIRING
Cable 1.0 mm CSA Max length 300 metres
Cable 1.5 mm CSA Max length 450 metres
5.2 APPROVED DETECTOR TYPES
Sirius II has been tested with the following detectors and call points:
Apollo Series 60 and Series 65
Hochiki CDX range
Nittan Sensortec
Nittan Evolution
KAC manual call point
5.3 TECHNICAL SPECIFICATIONS
Size: H: 280 mm W: 350 mm D: 90 mm
Weight excluding batteries 2 kg
Operating temperature -5 deg C to 40 deg C
Operating humidity 5% to 95%